siemens MP 277 10" touch screen issue

Soonam

Member
Join Date
Apr 2016
Location
south korea
Posts
2
Hello Iam using siemens MP 277 10" touch screen on the Siemens S7 315-2DP PLCs DP port along with other remote IOs. The issue iam facing right now is when i try to connect the Touch screen on the DP network whole DP network going down. I did check the profibus adress all looks good . What will be the reason
 
Depends on the network, only the last device on both sides of the network need the termination to be on. All other resistors need to be off.
 