OpsEng Member O Join Date Mar 2017 Location Pa Posts 2 Apr 6, 2017 #1 How do I? "LVA_SW1_SPD_REMOTE" "LVB_SW1_SPD_REMOTE" JC If first line is =1 or second line =1 Jump _003: \used to stl
How do I? "LVA_SW1_SPD_REMOTE" "LVB_SW1_SPD_REMOTE" JC If first line is =1 or second line =1 Jump _003: \used to stl
Bratt Lifetime Supporting Member B Join Date Nov 2003 Location West Sweden Posts 726 Apr 6, 2017 #2 Code: O "lva_sw1_spd_remote" O "lvb_sw1_spd_remote" jc _003
Bratt Lifetime Supporting Member B Join Date Nov 2003 Location West Sweden Posts 726 Apr 6, 2017 #3 If the variables are numeric and not booleans assuming its Siemens STL Code: O( L "LVA_SW1_SPD_REMOTE" L 1 ==I ) O( L "LVB_SW1_SPD_REMOTE" L 1 ==I ) JC _003 Last edited: Apr 6, 2017
If the variables are numeric and not booleans assuming its Siemens STL Code: O( L "LVA_SW1_SPD_REMOTE" L 1 ==I ) O( L "LVB_SW1_SPD_REMOTE" L 1 ==I ) JC _003
OpsEng Member OP O Join Date Mar 2017 Location Pa Posts 2 Apr 6, 2017 #4 Thank you I'm sure it seems trivial....but on my end not so much. Greatly appreciated, now I remember why I like this site so much!
Thank you I'm sure it seems trivial....but on my end not so much. Greatly appreciated, now I remember why I like this site so much!