Now, I am working on a project where I need to communicate AB plc with a siemens one. I actually get them communicate with each other but I have a question about swapping.
For example, when sending a dint value(temperature etc) to siemens plc, I need to swap it but there are also dword values which I created bool by bool (start,stop, etc) but they are sent as dword to siemens side. When sending this dword value it is not needed to swap.I didnt understand the reason of this. Dont they recorded memory in same manner ? Why they both dont need swap ?
Thanks in advance.
For example, when sending a dint value(temperature etc) to siemens plc, I need to swap it but there are also dword values which I created bool by bool (start,stop, etc) but they are sent as dword to siemens side. When sending this dword value it is not needed to swap.I didnt understand the reason of this. Dont they recorded memory in same manner ? Why they both dont need swap ?