panel1 Member P Join Date Nov 2004 Location North Carolina Posts 24 Apr 13, 2007 #1 I think I read somewhere that up to (4) 1762 I/O modules could be connected to a Micrologix 1100. Could someone verify this. Also does it matter in what order they connect as long as my addressing reflects their current position?
I think I read somewhere that up to (4) 1762 I/O modules could be connected to a Micrologix 1100. Could someone verify this. Also does it matter in what order they connect as long as my addressing reflects their current position?
Donnchadh Lifetime Supporting Member D Join Date Jun 2002 Location Ireland Posts 1,004 Apr 13, 2007 #2 micro logix 1100 Hi You are right in all cases.You can add up to 4 cards and it does not matter what order you have them. Donnchadh
micro logix 1100 Hi You are right in all cases.You can add up to 4 cards and it does not matter what order you have them. Donnchadh
Tom Jenkins Lifetime Supporting Member Join Date Apr 2002 Location Milwaukee, WI Posts 6,301 Apr 13, 2007 #3 There is a confuguration assistance program available for download on the A-B site. A neat little tool!
There is a confuguration assistance program available for download on the A-B site. A neat little tool!