I have 313C Siemens PLC its working well But sometimes when it is in rum mod it go into Stop mode automatically whiout any alarm. What can be resons anybody can tell me about its fault.
 
Hi finskhan.

Sometimes when I am in RUM MODE, I also go into STOP MODE without forewarning :)

Anyway, you have to go online with the PLC and investigate its Diagnostics Buffer. It will tell you why it went from RUN to STOP.
 