Hi Folk,

What is the different between Simatic Softnet DP and Softnet S7?

I purchase from Siemens the Softnet Dp, 6GK 1704 5DW64 3AA0

when i install to workstation and run the Citect SCADA with CP5611,

S7 300 PLC , the NO LICENSE MESSAGE still pop up and ask me to buy

6GK 1704 5CW64 3AA0.

Any body can help on this?

Regards
 
Go to the Automation License Manager and in the middle of the screen click on "missing licenses" Its a drop down box
See whats missing and causing the message
 
Softnet DP is a rare piece of software. The big difference between the DP and S7 variants is that with DP you exchange data via socalled preconfigured i/o areas in both master and slave - whereas with S7 you have master-to-master comms, and the PC can access in principle any adress in the PLC.
Only advantage with DP over S7 is that DP can be much faster.
 

Similar Topics

Hi, I'm not a siemens expert but we recently converted an old siemens PC into a virtual machine so we could run it on modern hardware. It was...
Replies
16
Views
7,823
Hello everyone! We have a computer running on Windows XP 32 bits SP3 where Simatic Net Softnet IE 2008 Lean is installed, with C++ (VC6.0 and...
Replies
1
Views
1,407
Hello all, My clients asked me to pass hmi Powermeter information from our substation monitoring system to his ERP system. Our equipment is...
Replies
6
Views
4,515
Hello, I got 2 S7-200 communicating with each other and a computer with Simatic Softnet Lean 2006 communicating with both PLC. When...
Replies
1
Views
1,442
hello guys could any one tell me what is SIMATIC NET IE SOFTNET-S7 LEAN and SIMATIC NET IE SOFTNET-S7 basis used for ?
Replies
2
Views
5,163
Back
Top Bottom