Please help on software redundant for S7 300 siemen

asia548

Member
Join Date
Jun 2006
Location
Medan
Posts
12
I am installing software redundant, after downloading i got this problem:

1. Both CPU in stop mode:
- at first IM153-2 SF blink, ACT off.
- at second IM153-2 every thing is OK, ACT on
- SF and BF LED at both CPU are off

2. Switch CPU to RUN mode:
- SF LED on at both CPU
- at first IM153-2 SF blink, ACT off.
- at second IM153-2 every thing is OK, ACT on

Could anybody tell me what is wrong? i attach my hw config and network picture along with my program. DiagnoseA.txt and DiagnoseB.txt are the event i recorded from diagnose buffer of CPU A and CPU B respectively.
 
I got it,
emotion-2.gif


My program only have 2 IEC function block. instead of writing 2 at IEC LEN in OB100, i wrote 8. after changing it to 2 everything is fine.
 

Similar Topics

My client wants me to install GP-PROEX on their laptop so they can make changes on one of their screen in the future as needed. Their screens out...
Replies
5
Views
1,958
I need software driver Q2HBM110M . fix modify parameters for DRIVER model:Q2HBM110M, I don't know. where is software? fix setting programmes for...
Replies
1
Views
1,367
I need software inverter siemen. fix modify parameters for inverter model:1P 6SL3120-2TE21-0AA3, MADE IN SIEMEN I don't know. where is software...
Replies
2
Views
2,055
I need software inverter siemen. fix modify parameters for inverter model:1P 6SL3120-2TE21-0AA3, MADE IN SIEMEN I don't know. where is software...
Replies
0
Views
1,698
hi all, i have plc LS master-k80s and i need good software, because i don't found rising edge contact in KGL_win... thank u in advance...
Replies
5
Views
1,974
Back
Top Bottom