Panel view Plus comms

cornbread

Lifetime Supporting Member
Join Date
Feb 2007
Location
madison, indiana
Posts
407
Trying to set up the comms to a panel view plus 1000 using factory talk / RClinx classic. I want to use the serial port on my computer on the design tab. Tried just about every driver combo and not luck. Any help would be grealty appreciated.
 
You have to use RSLinx Enterprise that came with RSView Studio ME to set up comms on the PV+. It is not a separate executable, but a service that runs inside of RSView Studio. Look for "Communicatiosn Setup" in the prject tree on the left hand side of your screen when RSView Studio is open.
 
Tried that and I when I use the verify I get a message to no path to device has be made...or something like that... I get the exact message and post it later.
 

Similar Topics

Am asking if we can upgrade sd ram and cf card of panel view plus ab by a normal sd ram and cf card but Allen Bradley to save cost because in ab...
Replies
9
Views
280
Good morning, I have a question, I would like to know if I can send an Excel file to an email from my panel view and see how it is possible to...
Replies
1
Views
153
I want to run a factory talk view ME project in a Panel View Plus 7 Performance HMI. The project was developed in a 'Windows 7 Professional 64 bit...
Replies
5
Views
332
I purchased a used PanelView Plus 1000 to learn get familiar with the software. Seems to be a pretty popular HMI. I can ping the HMI but I cannot...
Replies
6
Views
881
Hello, hope yall are doing well. I have a HMI program where I need to add a "GoToDisplay" button, so when this button is pressed, it goes to a...
Replies
5
Views
880
Back
Top Bottom