mitsu plc problem

Join Date
Jan 2006
Location
manila
Posts
57
I would appreciate any help with my problem with this A2N MISTSU PLC. On the main board contain the PSU, A2NCPU, 3 input modules AX41 at slot 0-2 (32points)slot and 2 Special modules AD61 at slot 3-4. There's an extension board A55B with the leftmost output module AY13 (32 points) at slot 8, followed by another AY13 slot 9, then AY41 (32points) slot 10, then AY40 (16pts) slot 11 and last module AX40 (16pts) slot 12. PLC parameter i/o config. from gx developer as follows:
slot 0: input 32 points
slot 1: input 32 points
slot 2: input 32 points
slot 3: special 32 points
slot 4: special 32 points
slot 5: empty 32 points
slot 6: empty 32 points
slot 7: empty 32 points
slot 8: output 32 points
slot 9: output 32 points
slot 10: output 32 points
slot 11: output 16 points
slot 12: input 16 points

The problem is, when I monitor the outputs starting from y100 and so on from the extension board at my laptop, I could see that they were triggerred but the physical output is still off.
The last input module on the extension board had no problem, I could see them on and off when sensors are triggered. What seems to b the problem?

thanks in advance.

jap
 

Similar Topics

I don't understand command plc mitsu M7613----------[+P K7001 D1910 D888] help me
Replies
1
Views
1,594
Hello Guys, I need help. I encountered a machine with fx2n-64MR plc. I want to modify some sequence but unfortunately it is in ROM operation and...
Replies
5
Views
2,310
Hello all, this time is my question somehow theoretical, but with high practical impact. Let asume we have simple program and we have to...
Replies
6
Views
2,283
I am a newbie in Mitsu-PLC program . I teach myself with this . Please help me with this situation . I use Function PLSY with edit mode as...
Replies
7
Views
2,363
Hi, I am new to Mitsu, know RSLogix 500/5000, micros, etc, and am translating a dynamometer controller application from RSL5000 to GX Works2 on a...
Replies
2
Views
6,043
Back
Top Bottom