Hello,

I am new to this forum and I was wondering what I need to do to get my computer to connect with a remote plc through a 56 k modem. I am using microwin v4.0 sp 3 . My modem dials in , I get the connection but can never upload from the plc. Any suggestions would be appreciated.

thank you
 
What type of modem are you using? Most common modems can't use an 11-bit frame. Most industrial modems are capable of handling 11-bit frames.

What type of RS232-PPI converter are you using? The older ones can only be set to 11-bit frames, the newer ones can also be configured for 10-bit frames.

Kind regards,
 