Hello everybody...
I was wondering If someone can help about ControlLogix..
I have been trying to communicate a CLogix (ENET/B) and a PLC5/40E (Ch2, 10BASET Transceiver) using a ethernet link...
In the Clogix I am receiving a error message (MSG Box) number 301 about No buffer memory...
I am using a MSG type:
PLC5 Typed Read
Source Element: N7:0
Number of Element: 3
Destination: Array_[0]
Path: EthernetModule,2,130.130.130.180 (PLC5)
CIP Checked.
First I was receiving a error message 312 "Link address not available".. I changed the IP dest address for 1, which it's the Processor Node configured in the PLC5 (System Options)..
The new path is: EthernetModule,2,1
Now I am receivein the error 301 No buffer memory..
Does anyone knows How to fix this error?.. why it's happen?
Thanks in advance
Patrick.