Citect with Q series timer

ALAN001

Member
Join Date
Apr 2010
Location
UK
Posts
30
When I try to use a Timer with a Mitsubishi Q series PLC and Citect SCADA it wont compile it gives Bad IO Device Variable

Have used this to view running time before with FX PLCs and had no problems

Address: T10
Device type: INT


Timer.jpg
 
Try using TC 10 for the timer, TS10 for timer up bit, not sure but in GXIEC you use TC,TS,TN for timer functions within the plc
 