op7 backup with prosave

necyil

Member
Join Date
Nov 2004
Location
Turkey
Posts
102
Hello

I want backup pooram from op7 with prosave. How i go Transfere mode? Whith whick keys?

Pls help

Best regards

Nec
 
Nobat answere me..i find that

To get the configuration from this device to a pc:


1) Configure a cable with a DB9 female and a DB15 male

DB 15 (OP7 side) DB9(PC side)
3------------------------------->3
4------------------------------->2
12------------------------------>5

->1
|
->6
|
->4

->7
|
->8

(if this gets scrambled because of email, the pins are (DB15 male on OP
side) 3,4,12 to (DB9 Female on PC side) 3,2,5 with PC side 1 to 6 to 4
shorted and 7 to 8 shorted, you can also look up Siemens help entry
id:37191)


2) On a PC with Simatic ProTool Pro CS, navigate to
C:\siemens\Protool\utility and run "prosave.exe" (this is assuming default
installation path)


3) The dos window will detail the selected target, if it is not
op7/op17/td17... select F5 to select target, then F3.


4) On the OP7 (still powered off) press and hold the up-arrow key and the
esc key at the same time, continue to hold and power up the OP7. After
power has been on a couple of seconds, release both keys. There should be a
screen on the OP saying that it is ready to transfer


5) On the PC, create a directory on a drive (probably Dos 8.3 compliant, no
long names) such as c:\OP7


6) From the prosave utility, select F2, backup data


7) The utility will ask for filename, enter the path and a filename such as
c:\op7\cmop7 and hit enter

<P>8) The transfer should start, it takes a couple of minutes, there should be
a scrolling line at the bottom of the OP7


9) When the transfer is complete, hit esc on the OP7 and the start screen
should come up


To get the configuration from a PC to an OP7<br>
1) Use same cable as above<br>
2) If it is new OP7 with no configuration, when the OP7 is powered up, it
will be in transfer mode. If there is a configuration on the OP7, with the
OP7 powered off, press esc + right-arrow + down arrow at the same and power
up the OP7 as before. This key combination ("overall reset") deletes the
configuration
memory. The OP then switches to download mode and waits for data to be
downloaded from the PC.<br>
3) On a PC with Simatic ProTool Pro CS, navigate to
C:\siemens\Protool\utility and run "prosave.exe" (this is assuming default
installation path)<br>
4) The dos window will detail the selected target, if it is not
op7/op17/td17... select F5 to select target, then F3.<br>
5) From the prosave utility, select F3, restore data and enter in the path
and filename of the file to transfer<br>
7) The transfer should start, it takes a couple of minutes, there should be
a scrolling line at the bottom of the OP7
 

Similar Topics

Hi guys, I was trying to upload the program from op7 to my pc but I was not successful. When i am trying to upload the program this time op...
Replies
20
Views
7,489
I have converted a Siemens OP7 program to a new Delta DOP107BV. It is all working as expected except for the timer values. I am using MW36 as the...
Replies
6
Views
937
I have a customer who had a faulty Siemens OP7. They sourced a replacement. They have the original program. I downloaded the program to the...
Replies
10
Views
2,529
Hi Guys, Hoping we still have some Siemens Old hardware Gurus on here. We are trying to support one of our long time customers. Who have obtained...
Replies
4
Views
909
Hi all! I have this old Siemens Simatic op7 panel I need to rescue. At boot nothing appears on lcd, backligth and all led's are on. Does not...
Replies
0
Views
785
Back