DH+ cable length

LStewart

Member
Join Date
Apr 2005
Location
Mississippi
Posts
95
I could not find the answer to my question on the Rockwell website and am now hoping that someone may know the answer or have a link I can follow.
What is the maximum run distance that the blue hose for DH+ can be?
 
1770-CD (Belden #9463)
762 m (2,500 ft) @ 230,400 bit/s
1,524 m (5,000 ft) @ 115,200 bit/s
3,048 m (10,000 ft) @ 57,600 bit/s

whoops, Okie beat me to it.
 
I could not find the answer to my question on the Rockwell website and am now hoping that someone may know the answer or have a link I can follow.
What is the maximum run distance that the blue hose for DH+ can be?

Are you talking from end to end, or for a drop? In any case, I typed in DH+ in the Search Box at www.ab.com, and this was the first in the list. It should answer your questions, if not post again with specific questions.

http://www.ab.com/en/epub/catalogs/12762/2181376/214372/1491278/3404058/tab2.html

Stu....
 

Similar Topics

Anyone know off the top what the maximum cable length should be between a compact logix controller and some point I/O? I have 10 meters in my...
Replies
2
Views
1,546
I understand that 10/100 Ethernet recommends a max cable run of 100M (328ft). With something like industrial Ethernet IP, Does this still hold...
Replies
15
Views
4,247
Hello guys, I have an issue about maximum cable length calculation of a digital input on Siemens SM321 card. by calculation and according to...
Replies
8
Views
2,852
Hi everyone. I have a question about feedback cable for rotary servo motors MP series. I know that maximum cable length can be 90 meters but my...
Replies
1
Views
2,047
Hi Friends, Can any one help me to figure out the maximum length for a control cable. I have devices located around 150 meters away from the...
Replies
4
Views
1,484
Back
Top Bottom