When I save my program I receive the following message:

Warning: Associated RSNetWorx file name of device conflicts with associated file name of device at same node and slot in EtherNet/IP project file.

Any ideas. Thanks
 
It's mostly harmless.

Something is different between the module names in your RSLogix 5000 project file and those stored in a linked RSNetworx for EtherNet/IP file.

Go to the RSNetworx tab for your root EtherNet/IP module and re-associate or delete the link to a *.ENT configuration file.

Because RSNetworx for EtherNet/IP isn't necessary for 99% of the work I do, I don't link my EtherNet/IP modules to an RSNetworx project file, like I do with RSNetworx for ControlNet.
 
Yeah, I've also wondered what RNetworx for Ethernet WAS used for. I've nevered had a reason to use it.
 

Similar Topics

I am having difficulty doing something i do in every other plc without a problem I have created an SCL AOI. I have an integer input to it. Lets...
Replies
3
Views
1,610
Control Logix - L8 CPS Array[1], Array[0], 30. What I want to do is move everything up one. It is an Array of 31. IE Array[30] goes to...
Replies
11
Views
2,677
I'm trying to control a slow process where we only get an updated PV every 5-10 minutes. Right now we do a pseudo-automatic control that works...
Replies
7
Views
3,339
Hello all, I have a small programming issue for you. I have 6 250hp water pumps with 2 of them on VFD's. Engineers are wanting to automate these...
Replies
3
Views
2,781
I have recently made a career change after 25 years of being an electrician. I am officially a junior automation controls programmer. I recently...
Replies
11
Views
364
Back
Top Bottom