Recepies in Protool

NoName

Member
Join Date
Sep 2003
Location
Domžale
Posts
273
Hello all.

Here's the thing. I have 10 recipes in Protool,and I don't know how to configure the Data mailbox area pointer.Do I need to configure 1 Data mailbox for 1 recipie?If this is so,then I need to configure 10 Data mailbox area pointers right????

Thankyou
>Ales<
 
Hi
If it's a Windows based system (TP170 or similar)you just need one Data mailbox
It's 5 words long with the following structure:
Word 1 - Recipe number
Word 2 - Data record within that recipe number
Word 3 - Reserved
Word 4 - Transfer status (see below)
Word 5 - Reserved

The Transfer status has the following code:

0 - transfer ready, idle
2 - transfer in progress
4 - finished without errors
12 - Error occurred during transfer

Hope this helps
 
Last edited:

Similar Topics

Hello all. We've made 2 machines for our custumer. Now they expressed a wish that they could enter recepies with a computer not with the...
Replies
4
Views
1,879
Does anyone know where I can download the Simatic ProTool software? Thanks.
Replies
5
Views
1,524
Hello, I am trying to break in into project from 2012 because it may require some modifications. Currently I am in stage of trying to understand...
Replies
6
Views
2,400
Asking for a friend who has a Protool v1.0 project. He needs to migrate it, and for that he needs to first migrate to v2.51 which he does not...
Replies
2
Views
1,164
So I am working on a machine where the PC has died. The PC was running Windows XP, Protool RT, Step7 V5.3, SimoComU and other software. The...
Replies
9
Views
2,449
Back
Top Bottom