Hi Controls Gurus, same inherited system prompting my VersaPro version question, has a peculiar problem on the HMI, which may have surfaced when the computer running Cimplicity HMI suite was replaced. The CimView Screens include a login option for higher level users, allowing access to certain screens. Even after loggin in at SYSMGR level, when you try to access the "setpoint action" of certain variables, a message comes up saying "username and password not valid". I looked at the screen in CimEdit, but don't see any condition expression for the item on the screen. Is there another place within a Cimplicity project that I should look to see a login condition designated for changing a specific variable? This is a particularly irksome glitch, because it not only denies the user editing the variable value, but freezes the CimView screens, so the HMI computer must be rebooted! Thanks for any clues or suggestions where to dig deeper.