Hello,
I´d like connect Sick LUT9U-P120L to PLC AllenBradley CompactLogix L33ERM
Sick sensor has IO-Link communication, CompactLogix has Ethernet so I use Balluff BNI EIP-502-105-Z015, IO-Link to Ethernet converter.
Ethernet communication from CompactLogix to Balluff and vice verca is OK, but from Sick sensor I get only few data like measured value, output, vendor ID, device ID, but not get other like settings, status etc..
I suppose IO-Link comm is also OK, because in Balluff web server are full data from sensor. But I can not see data from sensor in PLC, I can not write data into sensor from PLC etc..
It seems that there even are not data blocks for these data..
I have idea, but dont know how to do it..
xml is file with sensor data description, but how to download it to Balluff or PLC.. ?
I will appreciate any advice or idea..