TIA Portal Coping Data From Input To DB

AF52

Member
Join Date
Apr 2010
Location
Lancashire
Posts
8
Hello
I am looking for some assistance in moving input data into a data block using Siemens TIA Portal V13.
I have a device connected via Profibus. I am receiving a total of 76 input bytes from this device starting at I1000 in the hardware data table.
I want, if possible, to copy all 76 bytes of data to DB300 with one instruction.
I have tried BLKMOV and UBLKMOV but can not get these instructions to work.
Does anyone have a better solution?
Thanks in advance.
 
Depending on which CPU you are using, and how it is configured, DPRD_DAT may work instead. It is under Extended Instructions -> Distributed IO -> Additional Instructions.
 