Hi All,

Anyone know what a STRUCT Type S5TIME is in Intouch tagname dictionary item? example PLC Step 7, DB19, Type, STRUCT is S5TIME and Initial value is S5T#3S, What would the item name be in the tagname dictionary, Intouch 10.5. Thanks in advance.
 
I am not sure about what you are after. But the format of a S5TIME is the same as a DINT with the two first bits indicating resolution:

0: 10ms
1: 100ms
2: 1s
3: 10s

I don't know how INTOUCH works. But S5T#3S could be represented as an 8195 DINT.
 