Panasonic AFP15201-US9

GG Controls

Member
Join Date
Jul 2015
Location
Cincinnati
Posts
2
I've got an antique Matsushita(Panasonic) FP1-C24 PLC that I need to connect to. I found the software, but I'm having trouble finding the AFP15201-US9 programming cable. I've been combing the web with no luck. Can anyone help?
 
The original cable is no longer manufactured. Below are the parts I had to purchase and assemble in order to connect to the Matsushita controller.


Parts for new cable:
Tool Port Cable: AFP1500-US
RS422 to RS232 Converter: SerialComm CON-422-PE9
RS232 to USB Interface: Omron CS1W-CIF31

AFP1500-US Connector: Hirose HR212-10LP-8P


AFP1500-US Connector Pinout
Pin Description Color
- FG Shield
1 SG Brown
2 TxDA(-) Red
3 RxDA(-) Green
4 ---
5 TxDB(+) Blue
6 RxDB(+) White
7 RTS
8 +5V Black
 

Similar Topics

hi everyone. i'm working now with panasonic PLC. The machine is OE, so I uploaded the file using FPWIN Pro 7 but when I open the program and try...
Replies
0
Views
655
I am involved with the Panasonic FP7 for my final year project. I am doing a water distribution system and I want to use interrupt program for the...
Replies
0
Views
724
Can someone tell me what I'm seeing here? I'm online with the FP2 and looking at some rungs with DT120 and DT124. Each are used twice and each...
Replies
7
Views
1,732
I'm working with a Customer that has 2 Panasonic FP2-C2 units. I'm not exactly sure what this even is... Is it a PLC with motion control or just...
Replies
6
Views
1,547
Currently working on a job for panasonic using FP-XH model PLC. I have finished my code and it seems to be working as expected (hopefully) :utoh...
Replies
2
Views
1,755
Back
Top Bottom