Good Evening ,

What type of output is coming from a Safety Light Curtain ? I took notice that normal relays will not work. I have all intentions of using a safety relay. Is it something like a pulse train ?

Thanks in advance
 
Its my understanding on the AB ones I've used that they are either relay or transistor outputs. The recommended safety relays are nothing special and are the same ones used for E-STOP push buttons.
 
OSSD1 and OSSD2 are redundant (typically transistor-based) outputs. You need to wire them to a safety relay/module that accepts dual 24vdc signals, like this one:
http://www.bannerengineering.com/en...nd-Modules/531/Universal-Input-Safety-Modules

Be careful in your selection; virtually all safety relays have dual inputs but many use a pulsed signal and are meant to be used with mechanical safety switches. The idea behind the pulsed signal is that a short circuit to 24v will not be mistaken as a valid "on" state, but it prevents usage of solid state outputs like those found on light curtains.
 

Similar Topics

Hi everyone! I'm working on the controls design of a semi-automatic pneumatic vertical press. The machine will consist of two double-acting...
Replies
4
Views
1,764
Good Morning , I was thinking of using a Guardshield Safety Light Curtain on a palletizer. The light curtain I was thinking of using is a...
Replies
0
Views
1,082
Hi, I'm new to the automation industry. While installing the light curtains what are the main factors to be taken care of? Is there any varying...
Replies
9
Views
3,273
This is probably a basic question but need some info. We have several pairs of light curtains that the OSSD outputs go into the safety PLC and...
Replies
4
Views
3,415
Good Evening , I have some Rockwell Light Curtains and Guardmaster 440C-CR30 Configurable Safety Relays . I was wondering if there is any...
Replies
2
Views
1,379
Back
Top Bottom