Search: Posts Made By: Stuwertz
Forum: LIVE PLC Questions And Answers March 3rd, 2020, 12:19 PM
Replies: 12
Views: 1,466
Posted By Stuwertz
Thanks everyone those your inputs. In final we...

Thanks everyone those your inputs. In final we replaced that power flux 70 drive then issue solved .



How we found that power flux 70 only having issue ? Two months before this power flux 70...
Forum: LIVE PLC Questions And Answers January 14th, 2020, 03:03 PM
Replies: 12
Views: 1,466
Posted By Stuwertz
Hi , We are facing f71 error on power flux...

Hi ,

We are facing f71 error on power flux 40 drives. And also now the one resistor connected on node 12 but physical end . Either it should be node 14.
Forum: LIVE PLC Questions And Answers January 14th, 2020, 04:59 AM
Replies: 12
Views: 1,466
Posted By Stuwertz
Hi mr. Ken , Today I...

Hi mr. Ken ,

Today I installed resistor and I checked the values between can H and can L it shows 61.3 ohms . But again itís bad luck to us we are facing still F0071 on...
Forum: LIVE PLC Questions And Answers January 13th, 2020, 05:20 AM
Replies: 12
Views: 1,466
Posted By Stuwertz
Hi mr ken . I checked in devicenet...

Hi mr ken .

I checked in devicenet remove able devicenet female connector itís seperate two lines . In one line resistor connected at end . But in other line There is no resistor . Is...
Forum: LIVE PLC Questions And Answers January 11th, 2020, 03:04 AM
Replies: 12
Views: 1,466
Posted By Stuwertz
Hi mr. Ken . I checked...

Hi mr. Ken .



I checked that one resistor terminated on physical extreme end. I will double check the exact resistance values and how may resistors connected then i will update to...
Forum: LIVE PLC Questions And Answers January 10th, 2020, 04:30 PM
Replies: 12
Views: 1,466
Posted By Stuwertz
Hi mr.Ken Please find the answers on each...

Hi mr.Ken

Please find the answers on each questions



Does a network error code also appear on the DeviceNet scanner or in its Status tags, as well as on the drives ?
While error on power...
Forum: LIVE PLC Questions And Answers January 10th, 2020, 03:10 PM
Replies: 12
Views: 1,466
Posted By Stuwertz
Power flux error 71 on devicenet network

I have running devicenet network consist of 1796-SDN and 14 powerfexes, three consits of power flux 700 and remaining consits of power flux 40 .
The problem is during the line operation F71 occurs...
Showing results 1 to 7 of 7

 