Search: Posts Made By: jonney
Forum: LIVE PLC Questions And Answers July 1st, 2018, 10:40 PM
Replies: 6
Views: 688
Posted By jonney
Final confirmation is license problem. Intouch 10...

Final confirmation is license problem. Intouch 10 doesn't support ABCIP.5, the max. version is ABCIP.4 SP2.
Forum: LIVE PLC Questions And Answers June 8th, 2018, 09:20 PM
Replies: 6
Views: 688
Posted By jonney
I got the hot fix file HF-L00137689.exe contains...

I got the hot fix file HF-L00137689.exe contains DASABCIP.dll.
I will feedback later.
Forum: LIVE PLC Questions And Answers June 8th, 2018, 12:49 PM
Replies: 6
Views: 688
Posted By jonney
It takes time for my local Wonderware branch...

It takes time for my local Wonderware branch response. Anyone has the hot fix number L00137689? Thanks.
Forum: LIVE PLC Questions And Answers June 8th, 2018, 11:16 AM
Replies: 6
Views: 688
Posted By jonney
We used 1756-ENBT/A which has good configuration....

We used 1756-ENBT/A which has good configuration.
Intouch 10 only read and write total 8 I/O Real data from L5571.

I think the problem comes from the known issue...
Forum: LIVE PLC Questions And Answers June 8th, 2018, 10:07 AM
Replies: 6
Views: 688
Posted By jonney
oops, it stop updating the Intouch I/O REAL again...

oops, it stop updating the Intouch I/O REAL again even though the heart bit is blinking (bit data is updating but I/O Real data is not updating).
Now I clear the Intouch historical data and switch...
Forum: LIVE PLC Questions And Answers June 8th, 2018, 04:31 AM
Replies: 6
Views: 688
Posted By jonney
Tech ABCIP.5 lost connection some time with 1756-L71 5570 Controller Rev.21.11

Environment:
MMI Side: Intouch 10, ABCIP.5 connects with one 1756-L71; ABTCP.1 connect with few PLC5 1785-40E
PLC side : 1756-L71 5570 Controller Rev.21.11, 1756-ENBT/A; PLC5: 1785-40E
...
Forum: LIVE PLC Questions And Answers September 14th, 2012, 04:28 AM
Replies: 19
Views: 9,697
Posted By jonney
The GML 3.9.1 is different with what you said....

The GML 3.9.1 is different with what you said. The auto tuning almost is rubbish without function. I can send you a cope of the software and my application.Please give me your email.

The...
Forum: LIVE PLC Questions And Answers September 8th, 2012, 01:46 AM
Replies: 19
Views: 9,697
Posted By jonney
Yes. I am doing commissioning on a new Lenze...

Yes. I am doing commissioning on a new Lenze motor and Lenze inverter to replace original HR2000 inverter and Reliance motor. But the Lenze motor is shaking,unstable,hot and OC. so I suspect some...
Forum: LIVE PLC Questions And Answers September 7th, 2012, 10:57 AM
Replies: 19
Views: 9,697
Posted By jonney
Motor Type confuguration

I have no clue to set up this parameter.
But according to my old line, this parameter is set by no uniform.
What are your thinking?
Forum: LIVE PLC Questions And Answers September 6th, 2012, 07:42 PM
Replies: 19
Views: 9,697
Posted By jonney
Not GML Commander. I used GML 3.9.1. In my old...

Not GML Commander. I used GML 3.9.1.
In my old program, someone set the Counts/Mtr Rev 10000 or 8192 or else. the encoder is 1024 PPR actually. But the program works,why?
Forum: LIVE PLC Questions And Answers September 6th, 2012, 01:55 AM
Replies: 3
Views: 4,067
Posted By jonney
Motor Type confuguration

I have a problem:
How to set Transducer Counts/Mtr Rev and Motor type for Drive/Motor 1394 configuration in GML 3.9.1 (IMC 1394 S Class Compact,4100-234-RL)? The motor is Lenze MCA21X17 with 2048PPR...
Forum: LIVE PLC Questions And Answers September 6th, 2012, 01:51 AM
Replies: 19
Views: 9,697
Posted By jonney
How to set Transducer Counts/Mtr Rev and Motor...

How to set Transducer Counts/Mtr Rev and Motor type for Drive/Motor 1394 configuration in GML 3.9.1 (IMC 1394 S Class Compact,4100-234-RL)? The motor is Lenze MCA21X17 with 2048PPR TTL Encoder (A,A...
Forum: LIVE PLC Questions And Answers July 3rd, 2012, 08:56 PM
Replies: 11
Views: 6,666
Posted By jonney
I read GML Commander V4.03's latest update...

I read GML Commander V4.03's latest update information. It says:

Version 4.03 is compatible With the following Motion Control Firmware:

1394 Turbo GMC System iCODE Firmware: V3.5 to V3.9
...
Forum: LIVE PLC Questions And Answers July 2nd, 2012, 09:26 AM
Replies: 11
Views: 6,666
Posted By jonney
In our V3.9.1's GML program, they chose iCode 3.3...

In our V3.9.1's GML program, they chose iCode 3.3 Compact /1394 instead of what the sticker on the cover wrote Firmware Revision: 303103.5B.
I can't find any doc about the explanation of...
Forum: LIVE PLC Questions And Answers July 1st, 2012, 09:48 AM
Replies: 11
Views: 6,666
Posted By jonney
The nameplate shows "Firmware Revision:...

The nameplate shows "Firmware Revision: 303103.5B". But In GML 3.9.1 shows the iCode Version is 3.3 Compact /1394 (Menu Definitions -> Control Options -> 3.3 Compact /1394 being checked ). What...
Forum: LIVE PLC Questions And Answers June 29th, 2012, 09:59 PM
Replies: 6
Views: 1,901
Posted By jonney
I got GML Commander V4.03. I can send you. Email...

I got GML Commander V4.03. I can send you. Email me at jonney3099 at gmail.com
Forum: LIVE PLC Questions And Answers June 29th, 2012, 09:04 PM
Replies: 2
Views: 1,743
Posted By jonney
Try to install GML 3.9.1 on Win9x. If you install...

Try to install GML 3.9.1 on Win9x. If you install on XP, you may need to stop the printer service.If you install GML 3.9.1 on Win7 or Win8,the Win7 & Win8 should be 32 bits OS.

If you still...
Forum: LIVE PLC Questions And Answers June 29th, 2012, 08:58 PM
Replies: 11
Views: 6,666
Posted By jonney
I used GML 3.9.1 to connect IMC S Class. IMC...

I used GML 3.9.1 to connect IMC S Class.

IMC S Class Compact
4 Axis Motion Controller
Options: Remote I/O,Axislink
Firmware Revision: 303103.5B
Serial Number: LE0FBDJY
Catalog Number:...