You are not registered yet. Please click here to register!


 
 
plc storereviewsdownloads
This board is for PLC Related Q&A ONLY. Please DON'T use it for advertising, etc.
 
Try our online PLC Simulator- FREE.  Click here now to try it.

---------->>>>>Get FREE PLC Programming Tips

New Here? Please read this important info!!!


Go Back   PLCS.net - Interactive Q & A > Search Forums

Showing results 1 to 25 of 500
Search took 1.99 seconds.
Search: Posts Made By: danw
Forum: LIVE PLC Questions And Answers November 9th, 2018, 11:50 AM
Replies: 4
Views: 133
Posted By danw
There are four assigned Modbus memory areas, as...

There are four assigned Modbus memory areas, as shown below:

(0)xxxxx, (coil registers)
(1)xxxxx, (Discrete Inputs status registers)
(3)xxxxx, (Input Registers)
(4)xxxxx, (Holding Registers)
...
Forum: LIVE PLC Questions And Answers November 9th, 2018, 09:35 AM
Replies: 4
Views: 133
Posted By danw
Function Code 03H reads from memory area...

Function Code 03H reads from memory area (4)xxxxx, known as Holding Registers, which are decimal numbers. The leading numeral (4) is not used in the Modbus message, it's only there so human beings...
Forum: LIVE PLC Questions And Answers November 8th, 2018, 01:39 PM
Replies: 12
Views: 541
Posted By danw
Someone asked for dual output thermocouple...

Someone asked for dual output thermocouple temperature transmitter on another forum and my response was that it's a big world out there and it might available, but I hadn't seen one yet.

Someone...
Forum: LIVE PLC Questions And Answers November 8th, 2018, 09:42 AM
Replies: 11
Views: 447
Posted By danw
The Siemens CLS100/200 capacitive point level...

The Siemens CLS100/200 capacitive point level sensors claim some discriminating sensing technology that can handle difficult level sensing apps.

I've used them for solids sensing - corn level...
Forum: LIVE PLC Questions And Answers October 22nd, 2018, 10:21 AM
Replies: 9
Views: 309
Posted By danw
0-20mA only applies to a 4 wire device, like an...

0-20mA only applies to a 4 wire device, like an analog output on a PLC, where the power to run the output electronics is supplied by the PLC.


4-20ma devices use the 3.6mA of the loop current...
Forum: LIVE PLC Questions And Answers October 17th, 2018, 07:18 PM
Replies: 13
Views: 4,719
Posted By danw
Hart is a master/slave protocol. My...

Hart is a master/slave protocol. My understanding is that the Moore Industries HIM acts as a HART master to poll the HART slave positioner to get the HART position data, which it then converts to an...
Forum: LIVE PLC Questions And Answers October 10th, 2018, 07:29 PM
Replies: 11
Views: 359
Posted By danw
Thanks for all the advice. Since it's one...

Thanks for all the advice.

Since it's one hole and I don't know when I'd do another, the knock-out punches lost out to a carbide tipped hole saw. The Ideal TKO brand has a number of good...
Forum: LIVE PLC Questions And Answers October 10th, 2018, 07:23 PM
Replies: 10
Views: 534
Posted By danw
RJ-45 connectors (standard for CAT cable) are...

RJ-45 connectors (standard for CAT cable) are used for all sorts of serial communications that is/are not Ethernet.

One has to be careful about what hardware is behind the RJ-45 connector. Back...
Forum: LIVE PLC Questions And Answers October 10th, 2018, 07:20 PM
Replies: 14
Views: 389
Posted By danw
I recommend an RS-485 isolator/repeater at the...

I recommend an RS-485 isolator/repeater at the master and half-way down a multidrop bus in order to

- protect the master in case of a fault hitting the 485 line

- protect half the multidrops...
Forum: LIVE PLC Questions And Answers October 10th, 2018, 11:35 AM
Replies: 11
Views: 359
Posted By danw
drill a 7/8" hole in SS for a 1/2" NPTM nipple

I need to drill a single hole (to pass a 1/2" NPTM pipe nipple) in a stainless panel/enclosure (already installed in the field, not in a shop).

Suggestions for a drill technique/tool?

I...
Forum: LIVE PLC Questions And Answers October 10th, 2018, 11:25 AM
Replies: 14
Views: 389
Posted By danw
Your inability to communicate with any drive...

Your inability to communicate with any drive suggests that when the VFD blew the doors off it might well have damaged the other devices on the communications bus (RS-485?).

I'd suggest that you...
Forum: LIVE PLC Questions And Answers September 26th, 2018, 08:00 AM
Replies: 12
Views: 839
Posted By danw
An Instrumentation Book Tony Kuphaldt's...

An Instrumentation Book

Tony Kuphaldt's Lessons in Instrumentation is a bargain - V2.3 is 3300 pages of text book level instruction in electricity, electronics as a background for process and...
Forum: LIVE PLC Questions And Answers September 15th, 2018, 12:52 AM
Replies: 5
Views: 482
Posted By danw
Does Beta tester ring a bell?

Does Beta tester ring a bell?
Forum: LIVE PLC Questions And Answers September 11th, 2018, 11:23 PM
Replies: 5
Views: 482
Posted By danw
It's a transit time ultrasonic flow meter. ...

It's a transit time ultrasonic flow meter. Entrained air (bubbles) or suspended solids are the enemy of transit time, scattering the energy in the ultrasonic 'beam'. An alternative like a PD meter...
Forum: LIVE PLC Questions And Answers September 10th, 2018, 11:21 PM
Replies: 3
Views: 460
Posted By danw
Thank you for your replies and efforts to locate...

Thank you for your replies and efforts to locate a radio. Such is Life. Dan
Forum: LIVE PLC Questions And Answers September 7th, 2018, 04:39 PM
Replies: 3
Views: 460
Posted By danw
Banner distributor? Looking for DX-80 RTD node radio

Looking for a 900MHz DX-80 node radio, old style or Performance, quad RTD inputs.

Any of the model versions below:

DX80N9X2S-P4 Performance, IP67 (SKU 18855 or 17448)
DX80N9X2S-P4C...
Forum: LIVE PLC Questions And Answers September 7th, 2018, 12:09 PM
Replies: 5
Views: 539
Posted By danw
I'm trying to recall if I ever traced a noise...

I'm trying to recall if I ever traced a noise issue to a DC power supply, and I can't recall one, and my experience goes back to older linear power supplies and the newer switch-mode power supplies...
Forum: LIVE PLC Questions And Answers September 6th, 2018, 05:05 PM
Replies: 5
Views: 478
Posted By danw
A man after my own heart. Totally agree.

A man after my own heart. Totally agree.
Forum: LIVE PLC Questions And Answers September 3rd, 2018, 02:52 PM
Replies: 7
Views: 446
Posted By danw
My experience is the same as diat150’s. All...

My experience is the same as diat150’s.

All the vendors offer an option for factory configuration (setting LRV/URV) or custom calibration to a specific range.

The ID tag can be stamped with...
Forum: LIVE PLC Questions And Answers August 30th, 2018, 12:45 PM
Replies: 6
Views: 649
Posted By danw
Modbus/TCP Client (Master) and server (slave) are...

Modbus/TCP Client (Master) and server (slave) are avaiable through either E1 or E2 Ethernet ports.

...
Forum: LIVE PLC Questions And Answers August 27th, 2018, 01:07 PM
Replies: 10
Views: 1,083
Posted By danw
Quote: Originally Posted...

Quote:
Originally Posted by AB2005 http://www.plctalk.net/qanda/images/buttons/viewpost.gif (http://www.plctalk.net/qanda/showthread.php?p=789172#post789172)
As...
Forum: LIVE PLC Questions And Answers August 26th, 2018, 05:56 PM
Replies: 3
Views: 3,901
Posted By danw
You can find information on Honeywell training...

You can find information on Honeywell training courses on their public web site



https://www.honeywellprocess.com/en-US/training/Pages/e-learning.aspx


Notice that courses are on the...
Forum: LIVE PLC Questions And Answers August 25th, 2018, 01:14 AM
Replies: 10
Views: 1,083
Posted By danw
A standard ”Limit-of-error” Type K thermocouple...

A standard ”Limit-of-error” Type K thermocouple has an accuracy of +/- 2.2 Deg C. ”Special Limit-of-error” reduces that to +/- 1.1 Deg C. Are your Chinese Type K’s Special Limit-of -Error?

An...
Forum: LIVE PLC Questions And Answers August 22nd, 2018, 10:44 PM
Replies: 6
Views: 649
Posted By danw
My bad. You're correct in using TCPS function...

My bad. You're correct in using TCPS function block. Slightly different setup than the RTU serial MBS FB, but the same basic concept.

...
Forum: LIVE PLC Questions And Answers August 22nd, 2018, 07:48 PM
Replies: 6
Views: 649
Posted By danw
If you are using the HC900 Modbus Slave Function...

If you are using the HC900 Modbus Slave Function Block (FB), then the HC900 is the Modbus Master/client who reads from the E&H recorder which is a Slave/server using the MBS and MBR Function Blocks. ...
Showing results 1 to 25 of 500

 
Forum Jump

All times are GMT -5. The time now is 01:33 PM.


.