FT View ME parameter file question

The solution I proposed works on ME and SE.
You would write {#1} or {#3} into the parameter list (not parameter file) on the go to display for the second level.
 
I’m using ME V10. This project is saved as 9.0 for a PV+7. There’s a couple YouTube videos on parameter passing I watched when I did this. When I created the connections, I browsed to Pump01.subelement then backspaced over Pump0 and replaced with #. Make sure you’re using a parameter file with any #1 and #2 definitions to the first window. Make sure it’s parameter list to the next window.
 
I don’t like the way I wrote that. It’s too late to edit. This is better:
Make sure you’re using a parameter file with any #1 and #2 definitions in the initial goto secondary window button. Make sure it’s parameter list in the goto window button from that window to the third level.
 
Old, but just to confirm. If you want subsequent displays to inherit the parameters of a parameter FILE, you do not specify a parameter file on those displays, you specify a parameter LIST which simply includes the numbers to inherit.
 

Similar Topics

Is there a way to select a parameter file when loading a given screen based on the value of a variable? I see that under "Global Connections" the...
Replies
2
Views
1,074
I am looking for some help in directly tagging parameter files on FT View SE. I have experience of directly tagging parameter files when using ME...
Replies
2
Views
2,456
I have a program that will have 20 parameter files for 1 page, and have 5 pages with 20 each. What i'm trying to figure out is how can i enable a...
Replies
5
Views
2,039
Is there anyway to pass a parameter file without using a Go To Screen button in FactoryTalk View ME? I am currently using multiple Go-To buttons...
Replies
0
Views
1,603
Hi everyone, Is there a way to put in the parameter file a parameter that is a negation of a tag ? For example: #1= NOT ValveClosed So when...
Replies
2
Views
1,351
Back
Top Bottom