Micrologix 1400 firmware email question

tacm

Member
Join Date
Jan 2008
Location
usa
Posts
105
Hi folks,

A recent change has our email port 25 blocked. This has been no problem with email from PC's, as we can specify another port in Outlook, etc. MicroLogix 1400 firmware hardcodes email to go out using port 25, with no way to specify another port. So our alerts no longer work. Has anyone else experienced this dilemma? Any workarounds?

Steve
 
If you have a router between the PLC and the mail server, you could configure the router to forward port 25 to the new address when the PLC triesto send data on port 25.
 
i have one question related to micro logic 1400 is that i am using it as a on-off controller right now.if i want to use that controller as a analog input read then where should i connect my sensor wire and in program what should i select?
 

Similar Topics

Hi, I've got a MicroLogix 1400 controller with a dead ethernet port. I'd like to update the firmware, but the download from Rockwell...
Replies
9
Views
6,805
Hi, I am working with a Micrologix 1400 model 1766-L32BXB. With no input wires connected to the “in12” thru “in19”, I am getting 24 volts while...
Replies
4
Views
178
Hi everyone, I hope I don't butcher this up, please feel free to critique me wherever if I do, I have an issue I would equate to "chasing...
Replies
4
Views
242
Hi everyone, I'm working on a project where I need to exchange data between a Siemens S7-1200 PLC and an Allen-Bradley MicroLogix 1400 PLC. The...
Replies
8
Views
486
I'm not super familiar with the Micrologix line of processors, but I am pretty familiar with RSLogix 500. I'm trying to simply copy a string to...
Replies
4
Views
265
Back
Top Bottom