View Single Post
Old February 2nd, 2016, 07:38 AM   #5
rdrast
Lifetime Supporting Member
United States

rdrast is offline
 
rdrast's Avatar
 
Join Date: Apr 2003
Location: South Carolina Lowcountry
Posts: 5,467
For setting "More than one" parameter, try using a structure. And "Direct Reference" tags are especially bad for parameter files, try putting your tags in the tag dictionary instead, referencing the PLC.

Even if the tags in the PLC aren't in a structure, you can still create one using folders in FTView...

Folder: HMI
Folder: HMI\MOP_SPEED
Tags in Folder MOP_SPEED: Current_Val, PB_Increase, PB_Decrease

The parameter file would just be: #1=HMI\MOP_SPEED\

Then the objects in the display are just #1Current_Val, #1PB_Increase, #1PB_Decrease.