PanelView compact 1000 (gray screen)

driverx

Member
Join Date
Mar 2021
Location
quebec
Posts
52
hi gay,
the hmi works normally, suddenly the screen turns gray and no display appears. when I click on the screen I see that the cursor moves to where I clicked.
and it also happens when I press the ACK ALARM or ACK ALL ALARMS button.
the only way to get it back to work is power cycle.
panelview catalog number:2711PC-T10C4D1.
any help plz..
 
Sounds like you are using a Close Display button on a Replace type display. Instead use either Goto or Return To buttons. Only use Close Display buttons with On Top displays.
 