FactoryTalk View-Difference between Test Application and Create Runtime

Rob S.

Member
Join Date
Sep 2008
Location
Maryland
Posts
739
Good Evening ,

I'm working on a FactoryTalk View ME project and I have my communication path setup with my L33 CompactLogix and when I do the test application it runs great , but when I Create the Runtime , it says it does not have a communication path. What is the difference between the Test Application and Creating the final Runtime ? I thought it was the same .

Thanks so much in advance ,
 
When you test the application, it uses the design communication path. When you generate a runtime application, it uses the runtime communication path. I would imagine this feature (having separate communication paths for design and runtime) exists so that it's easy to quickly test changes on the fly, without having to modify your path and then remember to change it back once you were done tinkering before downloading it to the HMI. It was probably a much bigger issue in Ye Olden Dayes when there was probably quite a different path from laptop-PLC than there was from HMI-PLC. Now that everything is usually on ethernet, it's not such a big drama, but the feature remains.

You can set the path up in the runtime tab of your communications setup manually, but to avoid that tedium there's the handy "copy design to runtime" button that exists to do exactly that. Click that button, save your changes, and you should be good to go.
 

Similar Topics

This question may be odd but I am a maintenance guy and just started with Rockwell automation software. I have got a computer from my new current...
Replies
2
Views
10,244
Hello, I'm using FactoryTalk View ME V10. I created a valve as a global object with multiple parameters and when the object is being used at the...
Replies
2
Views
129
Hello all, I was modifying an HMI in factory talk and went to change a go to display button using the ... to select from a list as I had done...
Replies
4
Views
163
Hello, We recently upgraded our control server to a newer model. After the transition we are experiencing issues with our trend graphs to where...
Replies
2
Views
120
Hi, I wanted to ask is there a way to have a visibility expression use the IP address of the HMI (Dynics, not PV) to show certain elements? The...
Replies
3
Views
200
Back
Top Bottom