1200 plc Motion control with BIAS option

adam_lhadi

Member
Join Date
Feb 2022
Location
algeria
Posts
59
Hi everyone

i have a delta VFD ,it's control signal is from 0..10V or in Mamps (no -10..10v)

my plc is 1251dc/dc/rly with analog output 0..20ma , i have used a 500ohm resistor to get the 10V

in order to use the motion control is it a must to have a VFD of -10..10V analog input and a plc of the same voltage rang -10..10V

in the vfd there is something called BIAS which give a result of (0 to 5V CW 5 to10 CCW)

can i use this feature instead of -10..10V
kind regards
 
Your problem is going to be that your Delta vfd needs to go forward and reverse with negative to positive reference.
Looks like Delta needs a digital input (MI number)

I assume your doing position control, not just speed control?
 
Your problem is going to be that your Delta vfd needs to go forward and reverse with negative to positive reference.
Looks like Delta needs a digital input (MI number)

I assume your doing position control, not just speed control?
yes my analog output is only 0..10V
 

Similar Topics

HI i would like to know how to get a variable that will store the amount of times a program has been executed. The issue is I have 3 DBs for 1 FB...
Replies
2
Views
49
Hi. I’m trying to upload program from existing PLC S7-1200. Create new project in TIA v15.1 then upload. After upload successfully, go online but...
Replies
5
Views
204
Hi Guys, I am trying to establish communication over profinet between Siemens S7-1200 PLC as IO device and codesys plc as IO controller. But I am...
Replies
43
Views
2,561
Hello members, I have Siemens S7-1200 PLC (CPU 1214C AC/DC/Rly version 3.0) and I want to get backup from it. I know how the procedure works. I...
Replies
0
Views
132
Hi! Please share firmware for 6ES7212-1BE31-0XB0 https://support.industry.siemens.com/cs/nl/en/view/64789124
Replies
7
Views
742
Back
Top Bottom