theColonel26
Lifetime Supporting Member
So I have a solenoid manifold with 9 solenoids Coils. I have 2 options for the E-Stop to kill them.
I can have the 24VDC going to the PLC Output switched by the E-Stop or I can have Switch the 0VDC from the Solenoid Coils
I'd kind of prefer to switch the 0VDC as it would give me more granular control on future panels about what is being killed by the E-Stop.
Is switching the 0VDC ok in a PNP Panel?
Thoughts?
I can have the 24VDC going to the PLC Output switched by the E-Stop or I can have Switch the 0VDC from the Solenoid Coils
I'd kind of prefer to switch the 0VDC as it would give me more granular control on future panels about what is being killed by the E-Stop.
Is switching the 0VDC ok in a PNP Panel?
Thoughts?
Last edited: