Modbus Communication
Hi everyone
i have a delta VFD-M series with RS-485 protocol RJ-11 (Modbus communication) and cm1241 rs-485 siemens module (6ES7 241-1CH32-0XB0) so i needed to transfer the DB9 connector to RJ-11 to establish the communication between the vfd and the plc the picture shows how i managed do adapt the two connectors please correct me if am wrong kind regards |
![]() |
![]() |
#2 |
Member
|
If DB9 pin 1 is truly signal ground, then yes, you have the correct connections.
I have seen other devices use pin 8 for A(-), pin 3 for B(+) and pin 5 for signal ground. Be aware that some manufacturers define the A and B driver lines backwards so that A to A and B to B does not work. If the driver lines are connected backwards, there's no damage, but communications will not work. The fix is to swap the lines on one end. |
![]() |
![]() |
Bookmarks |
Currently Active Users Viewing This Thread: 1 (0 members and 1 guests) | |
Thread Tools | |
Display Modes | |
|
|
![]() |
||||
Thread | Thread Starter | Forum | Replies | Last Post |
Modbus communication via modbus serial (485) to modbus tcp/ip | VISHALPATIL3.82 | LIVE PLC Questions And Answers | 4 | December 6th, 2010 11:56 AM |
Modbus Master not polling the Modbus Slave through an EtherNet/IP Connection | mihiri | LIVE PLC Questions And Answers | 3 | July 15th, 2010 03:41 AM |
ST-71 repeater panel modbus communication | sdmnishu | LIVE PLC Questions And Answers | 1 | September 10th, 2009 08:33 AM |
Simatic S7 - Modbus Communication | mareki | LIVE PLC Questions And Answers | 13 | November 22nd, 2007 08:11 AM |
Mitsubishi Q Series Modbus TCP module QJ71MT91 set up help req'd... | Pocko | LIVE PLC Questions And Answers | 0 | July 30th, 2006 03:45 AM |