Hello everyone, have you guys ever seen this issue?
plc - compactlogix 5069-l310erm rev 31.011
servo - 3 kinetix 2198-H070-ERS rev 7.001
switch - 1783-ems08t/B stratix 6000
automation network on port A2 of plc class C
enterprise network on port A1 of plc class B
As soon as I plug shopfloor into A1 or into the switch I loose the controller being the master clock and it becomes a slave. Eventually over time the clock jitter will fault out the servos.
I have tried the network in star/linear back to linear with the same results. I changed the switch to a stratix 8000 which supports cip sync. I have tried blocking ptp traffic to no avail. Without shopfloor communicating there is no issues with the clock.
Thanks.
plc - compactlogix 5069-l310erm rev 31.011
servo - 3 kinetix 2198-H070-ERS rev 7.001
switch - 1783-ems08t/B stratix 6000
automation network on port A2 of plc class C
enterprise network on port A1 of plc class B
As soon as I plug shopfloor into A1 or into the switch I loose the controller being the master clock and it becomes a slave. Eventually over time the clock jitter will fault out the servos.
I have tried the network in star/linear back to linear with the same results. I changed the switch to a stratix 8000 which supports cip sync. I have tried blocking ptp traffic to no avail. Without shopfloor communicating there is no issues with the clock.
Thanks.