Hi,I'm trying to migrate only CPU from PLC-5 to CLX and I/O modules are still PLC-5 series.
I think, the migration works is almost done but I have an issue.
Rack addressing method (1771-A4B, Dip SW setting) was 1/2 slot addressing.
I didn't change the rack addressing method.
And there were no any errors in CLX when i finished the migration
1756-DH/RIO module was OK too
But an active LED on 1771-ASB was blinking and I/O cards didn’t work.
So, I checked all settings but nothing was wrong.
Finally, I changed rack addressing method to 1 slot and then the active LED on 1771-ASB is fine and I/O cards are good.
How to use RIO communication between 1756-DH/RIO and 1771-ASB for 1/2 slot addressing type?
It must set 1/2 slot addressing because of field wiring and I/O Modules(1771-IBN,OBN) arrangement.
If I can't use it with 1/2 slot addressing, I should be reinstate the original state of this project
I think, the migration works is almost done but I have an issue.
Rack addressing method (1771-A4B, Dip SW setting) was 1/2 slot addressing.
I didn't change the rack addressing method.
And there were no any errors in CLX when i finished the migration
1756-DH/RIO module was OK too
But an active LED on 1771-ASB was blinking and I/O cards didn’t work.
So, I checked all settings but nothing was wrong.
Finally, I changed rack addressing method to 1 slot and then the active LED on 1771-ASB is fine and I/O cards are good.
How to use RIO communication between 1756-DH/RIO and 1771-ASB for 1/2 slot addressing type?
It must set 1/2 slot addressing because of field wiring and I/O Modules(1771-IBN,OBN) arrangement.
If I can't use it with 1/2 slot addressing, I should be reinstate the original state of this project
Last edited: