FactoryTalk freezing up
I'm developing a FactoryTalk SE local application on a Windows 7 platform communicating with a single MicroLogix 1400. When I invoke the 'command wizard', FactoryTalk freezes up and the wizard never appears. Task manager indicates 'Command Wizard Step 1 of 2' is running and when stopped, a box pops up with the error message "OLE 2.0 Load Failure".
I've tried removing and a re-install of FactoryTalk and setting Windows security so that 'Everyone' has full rights to all files. Anyone have a suggestion? Thanks - Walt |
![]() |
![]() |
#2 |
Member
|
What version of SE is it and what version of Windows 7, (professional?, 32 or 64 bit?)
|
![]() |
![]() |
#3 |
Lifetime Supporting Member + Moderator
|
Are you running multiple monitors ? Did you at one point ?
Command Wizard (and the Tag Browser) are notorious for remembering an Open position that's off the visible screen when you switch from multimonitor to single monitor. You can reset its launch position with a registry edit by deleting its Folder from the registry. Start > Run > Regedit >HKEY_CURRENT_USER\Software\Rockwell Software\RSViewSE\Application name\CommandWiz. |
![]() |
![]() |
#4 |
Member
![]() ![]() Join Date: Dec 2011
Location: Athens, GA
Posts: 23
|
Windows 7 Professional and SE 6.10.00 (CPR 9 SR 4). I did use two monitors initially, thought that might be the problem, and went back to two monitors to no avail. After following your registry deletion instruction, all is well again, although I don't understand why the second monitor didn't work.
You guys are the best and I greatly appreciate the quick advice. Walt Puryear Athens, GA |
![]() |
![]() |
#5 |
Member
![]() ![]() Join Date: Mar 2016
Location: Vancouver
Posts: 6
|
I had this same problem and plugging a monitor back in didn't help. Then I realized that since the position stays the same for the pop-up, maybe the previous monitor was in a different orientation or resolution. So I flipped the extended monitor to the other side like I have out on site and sure enough, the tag browser was there waiting for me. So try different positions if it doesn't work.
|
![]() |
![]() |
#6 | |
Member
![]() ![]() Join Date: Jan 2022
Location: Basque Country
Posts: 1
|
Quote:
Just had this problem and found another way. Instead of resetting you can force Tag Browser to appear by doing this: "Solution: One solution is to press the browse button, then execute the following keystrokes sequentially: 1. Alt-Space 2. M 3. Press the Left Arrow key <- until the browser appears." Extracted from https://www.elektroda.pl/rtvforum/topic1464367.html (here they talk about resetting launch position too) At first nothing appeared but I kept pressing the arrow and suddenly the window showed. Hope this's useful! |
|
![]() |
![]() |
#7 |
Member
![]() ![]() Join Date: May 2013
Location: Northern Snowball
Posts: 563
|
To do this in winXP+ Click the task bar icon for your errant program, or select its sub window. then press hold the Win Key and tap the left or right arrow key several times. This moves the window from screen to screen and can also attach it to a screen side so it takes up half the screen.
__________________
Problems that go away on their own mystically are not solved. They will return. |
![]() |
![]() |
Bookmarks |
Currently Active Users Viewing This Thread: 1 (0 members and 1 guests) | |
Thread Tools | |
Display Modes | |
|
|
![]() |
||||
Thread | Thread Starter | Forum | Replies | Last Post |
Running FactoryTalk View SE V5.0 to work with FactoryTalk Service Platform 2.40 ? | alpine | LIVE PLC Questions And Answers | 15 | December 15th, 2011 07:49 PM |
FactoryTalk View and MS SQL Server | Susanne | LIVE PLC Questions And Answers | 10 | October 14th, 2011 12:18 PM |
Annoyed with Allen Bradley / FactoryTalk Alternatives ? | RacerX10 | LIVE PLC Questions And Answers | 27 | October 1st, 2011 01:33 AM |
codesys V2.3 with FactoryTalk (OPC server) | Silence89e | LIVE PLC Questions And Answers | 11 | September 17th, 2011 10:50 AM |
FactoryTalk View Studio 6.1 SE Network Project, Display Component not Found Issue | tatsumasa | LIVE PLC Questions And Answers | 3 | September 2nd, 2011 06:54 PM |