Factory Talk SE Ver 10 Not working with PLC5's

CCM

Member
Join Date
Aug 2020
Location
West Virginia
Posts
1
I just upgraded a few of my servers to version 10 the upgrade worked fine but for some reason all my short cuts that I linked to PLC 5's will not populate any data. I have removed the short cuts, made different short cuts still nothing. these short cut run across a WAN witch might be an issue but all the micro and control logix on that and other subnets work fine. it is always the PLC5's. Can somebody please help
 
What driver are you using for comms to the 5?
I had issues with non-ethernet PLC5's, and ended up just messaging everything over to a ControlLogix controller :/
 
And what Firmware versions are the PLC5 units?

I came across an issue a few years back where certain firmware of PLC5 would not communicate with ControlLogix, once updated they were fine.
 

Similar Topics

I have some global objects, numeric display with associated data that pulls up a pop up screen. for the life of me i cannot figure out how it...
Replies
3
Views
232
Hey, I have factorytalk studio ME version9.it will generate "unable to communicate with the factory talk linx server localhost" every time I try...
Replies
3
Views
3,654
Hi All! I have the license for 100 displays - product FT View Server SE 100D License SFW, catalog number 9701-VWSS100AENE. How to know the number...
Replies
2
Views
1,276
How to fetch data from Microsoft sql server into ftv? I wanted to create form and store all the data into sql database... Also i need to search...
Replies
1
Views
5,201
Dear Experts, i need an urgent help of you. i had installed FTView about 6 months ago, it was working fine. but few days ago when i started...
Replies
3
Views
2,003
Back
Top Bottom