This may be a dumb question but can I use a 1756-BA2 in place of the 1747-BA for a SLC 5/04? The reason I ask is that we stock the 1756-BA2 in our spare parts.
 
No the connection is different from the BA2 to the BA, see the details of the ones we sell below... they are also cheap and small enough to stock the correct one

1747-BA
Type: Lithium
Voltage: 3.0
Capacity: 1200 mAh
Color: Black Heat Shrink
Size: 0.58" diameter x 1.04" long

1756-BA2
Type: Lithium
Voltage: 3.0
Capacity: 1200 mAh
Color: Black Heat Shrink
Size: 0.68" dia. x 1.38" tall

1756-BA1
Type: Lithium
Voltage: 3.0
Capacity: 1800 mAh
Color: Black Heat Shrink
Size: 0.68" dia. x 1.38" tall

The BA1 has the same connection but the size is not the same and will have a hard time fitting in the holder

bas.png
 
Last edited:
Yeah, I thought the connection was the same but I guess not. There can't be any sort of standardization, that would make things too simple.
 

Similar Topics

How has your experience been using non-Allen Bradley 1756-BA2 batteries? Would you use them in all instances, or limited applications? Any other...
Replies
16
Views
5,041
Good Afternoon , We have a ControlLogix 5561 controller. The maintenance group , powered down the machine and lost the program. The battery...
Replies
5
Views
5,044
Is there any difference between these batteries other than the connector style? We have a ControlLogix L61 processor with a dead 1756-BA2 battery...
Replies
3
Views
14,344
Hi, I have two quick questions: 1- Could I use 1756-IA16/A with TTL inputs? Sourcing (PNP)? Sinking (NPN)? Either one? 2- What does /A in the part...
Replies
6
Views
119
Hi all, installed on chassis A17 an A/I from Allen-Bradley , problem is what ever I do , all channels are sticked on value 39.9 and cannot change...
Replies
1
Views
122
Back
Top Bottom