Good day,
I have tried it. works like MAGIC. Thank you very much Milspecelectrician |
![]() |
![]() |
#18 |
Member
![]() ![]() Join Date: May 2002
Location: Kalamazoo MI
Posts: 2,324
|
Group 145 is not part of the visible parameters and therefore will not appear in any public-accessed Instruction Manual document.
Group 145 is part of the "hidden parameter" world and not generally available for any purpose. |
![]() |
![]() |
#19 |
Member
![]() ![]() Join Date: Mar 2014
Location: toronto
Posts: 1
|
Depends how you program it, But normally its just an alarm.
|
![]() |
![]() |
#20 |
Member
![]() ![]() Join Date: Sep 2016
Location: Scotland
Posts: 1
|
ACS800 Fault Code
Hi there,
I have changed out an existing VFD ACS800 to replace a faulty VFD ASD800, I changed all the parameters to suit the what the faulty VFD had originally. When attempting to test the unit, we get the fault code I/O COMMS ERR (7000) Has anyone got any ideas of how to get rid of this fault code, and what it actually means. Many thanks |
![]() |
![]() |
#21 | |
Member
![]() ![]() Join Date: Aug 2014
Location: Western Norway
Posts: 17
|
Quote:
![]() |
|
![]() |
![]() |
#22 | |
Member
![]() ![]() Join Date: Apr 2017
Location: india
Posts: 2
|
Quote:
When I change the passcode to 2303 it changes back to 1, what could be the reason ? |
|
![]() |
![]() |
#23 |
Member
![]() ![]() Join Date: Apr 2017
Location: india
Posts: 2
|
hi,
"..." Should appear for a brief moment this is not happening as soon as we change it to 2303 it changes back to 1 ! what is the possibility ? |
![]() |
![]() |
#24 | |
Member
![]() ![]() Join Date: Jul 2017
Location: Dong Nai
Posts: 1
|
Quote:
![]() ![]() |
|
![]() |
![]() |
#25 |
Member
![]() ![]() Join Date: Aug 2014
Location: Western Norway
Posts: 17
|
|
![]() |
![]() |
#26 | |
Member
![]() ![]() Join Date: Oct 2018
Location: Beirut
Posts: 1
|
Quote:
as for the manual it says 1.44 , but 44 sub-menu is not exist. following your solution fixed the problem. thank you. |
|
![]() |
![]() |
#27 |
Member
|
This does not seem to work. Have tried both in drive windows and the front panel setting from 0 to 2303 but it just reverts back to 0 with no change to parameters?
Weird one about half of our drives have the same parameters hidden and the other half are accessible and done compare against the different drives there is not much difference that stands out. |
![]() |
![]() |
#28 | |
Member
![]() ![]() Join Date: Oct 2019
Location: El Salvador
Posts: 1
|
Totally works
Quote:
I was searching in the user manual but I couldn't find that failure. Any ideas, please. Thanks in advance |
|
![]() |
![]() |
#29 | |
Member
![]() ![]() Join Date: May 2022
Location: Chicago
Posts: 1
|
Quote:
|
|
![]() |
![]() |
#30 |
Member
![]() ![]() Join Date: Nov 2003
Location: NorthWest
Posts: 12
|
ACS800 PWR Mod Fan Hrs Reset (Alarm 4280)
ACS800 Only. See note on ACS880
Parameter numbers are different depending on the firmware you have in the drive. ACS880 Systems Firmware: 1) Parameter 1.30 = hour of power module fan runtime. Trip at approximately 60,000 hrs. Generates alarm 4280 "REPLACE FAN" 2) After replacing fan (recommended) Reset the counter: (a) Set Parameter 16.03 = 2303 (will go back to 0) (b) Set Parameter 16.09 = 1 (c) Verify that Parameter 1.30 had reset to zero (d) Set Parameter 16.03 = 358 ACS880 Standard Firmware (off the shelf): 1) Parameter 1.44 = hour of power module fan runtime. Trip at approximately 60,000 hrs (7yr). Generates alarm 4280 "REPLACE FAN" 2) After replacing fan (recommended) Reset the counter: (a) Set Parameter 16.03 = 2303 (will go back to 0) (b) Set Parameter 16.12 = 1 (c) Verify that Parameter 1.44 had reset to zero (d) Set Parameter 16.03 = 358 For the DCS880 just press the reset button on the keypad module for >3sec. |
![]() |
![]() |
Currently Active Users Viewing This Thread: 1 (0 members and 1 guests) | |
Thread Tools | |
Display Modes | |
|
|
![]() |
||||
Thread | Thread Starter | Forum | Replies | Last Post |
ABB ACS800 & Ethernet | Elcan | LIVE PLC Questions And Answers | 5 | May 20th, 2013 11:06 AM |
ABB ACS800 Drive | Rob S. | LIVE PLC Questions And Answers | 8 | March 19th, 2013 06:00 PM |
ABB RETA-01 to ACS800 firmware compatibility | Purrdie | LIVE PLC Questions And Answers | 3 | October 24th, 2011 11:02 PM |
ABB ACS800 LC firmware | TOKG1Tech | LIVE PLC Questions And Answers | 3 | June 14th, 2011 09:13 PM |
ABB ACS800 A1>min Fault (8110) | thebuzz | LIVE PLC Questions And Answers | 9 | May 14th, 2011 10:13 AM |