Communicate GE Workbench 5.0 with Series 90-30 PLC

Join Date
Jul 2014
Location
India
Posts
8
Hello friends,

I'm facing an issue while communicating cimplicity HMI 5.0 with GE PLC Series 90-30. Scada backup provided to me is using protocol series 90 Ethernet, the problem is when i start the project and check the device (quickview) i'm getting device down.

I've also tried by creating a new project with s90 triplex to communicate but no success.

While communicating from versapro 2.0 for logic it's communicating with PLC, so can't say Port is faulty.

Thanks in advance.
 
Are you also using an Ethernet connection for VersaPro or are you using serial communications for that? For Ethernet communications with the PLC are you using a CPU with a built-in Ethernet port or an Ethernet communications module?

Version 5.0 is a very old Cimplicity release. VersaPro is very old PLC programming software. How old is the PLC?
 
I'm using Ethernet connection. yes, CPU is having inbuilt ethernet port through which i'm trying to communicate.

Yes, it's very old versions used by one of my customer. o_O
 

Similar Topics

We are trying to poll data coming from a PLC for remote monitoring we have the IP address of the PLC and the default port number and the path is...
Replies
25
Views
543
We have some very old technology in my plant that needs adjusted but I don’t have the equipment. Can anyone tell me what I need to program this IO...
Replies
13
Views
323
Hi Guys, I want to connect my 1769-L36ERM to a different network domain, is it possible to do it using only the dual ports in the Controller? Or...
Replies
3
Views
202
Hi everyone, I'm working on a project where I need to exchange data between a Siemens S7-1200 PLC and an Allen-Bradley MicroLogix 1400 PLC. The...
Replies
8
Views
585
Good Evening , I have version 28 of Studio 5000 from a few years ago . If I got a new CompactLogix CPU , what is the lowest version of...
Replies
4
Views
463
Back
Top Bottom