FactoryTalk View ME and the PanelView Plus terminals use a third party driver set from Kepware, which they package and include at no additional cost. If you're using FactoryTalk View SE, the big distributed HMI, the drivers are a separate item.

You have to configure the drivers separately and treat KepServer basically like an OPC server.

The "KepServer Enterprise" bundle of drivers that's included with FTView ME is a subset of the larger KepServerEX product.

I believe that KepServer Enterprise includes a Beckhoff TwinCAT driver but.... the RA Knowledgebase is down right now and I don't have a full copy installed.

So when the Knowledgebase comes back up, search the terms "PanelView Plus Kepware Drivers" and look at the list.

An additional important note: the PanelView Plus "Compact" and the PanelView Plus 7 "Standard" models support only one driver at a time, whether A-B or third party. If you need to connect to multiple controllers, get a normal PanelView Plus 6, or the "Performance" model of a PanelView Plus 7.
 

Similar Topics

Hi everyone, This is my first time posting, so please forgive any omissions or mistakes. I am attempting to control the velocity of a stepper...
Replies
18
Views
990
Hello sameone have Beckhoff PLC Siemens Sinamics V90 configuration example?
Replies
0
Views
97
hello, I am using Beckhoff with TwinCAT3 and when I change or add some new hardware or for any reason, there is a mismatch in the real hardware vs...
Replies
1
Views
125
I have a Beckhoff CX7000 IPC with some digital I/O built-in and I additionally need two analog inputs 0-10V. Can I install both Ethernet terminals...
Replies
4
Views
205
Hello, We are currently working on a project that involves connecting a linear potentiometer to our Beckhoff PLC. After researching, we...
Replies
2
Views
193
Back
Top Bottom