Uploading Stratix 5700 to Project Issues

Deeter25

Member
Join Date
Apr 2016
Location
Pennsylvania
Posts
3
I'm trying to do an upload of the switch config files into the project but I get an error message saying 'Configuration session is already owned by another device'. Has anybody had this issue? I've contacted Rockwell tech support and the tech said he's never seen it. He didn't have any recommendations at the time either.
 
This happens if you have device manager open or another controller has an active DATA type connection to the Stratix.
If I recall correctly, CIP object timeout is set to 10 minutes, but I am not sure about Device manager.
 