First time using AB Micro850 - out of the box and powered up "MS" and "FAULT" are flashing. Connected via USB but cannot connect to the PLC. Tried to update firmware and get failure because PLC is not in right condition
 
Any modules plug into it?

EDIT: Try plugging it into a router, the router will assign a IP address and then see if you can see it in RSLinx via ethernet
 
I just learned with the addition of an expansion module, and end of bus terminator is required; this may be the problem. Ordered one, and will install next week
 
If you do wind up updating the firmware don't use the USB connection. I've had a very high failure rate with the ControlFlash program when using a USB connection and from what I understand it is a known issue. Use the USB to configure the Ethernet port and connect ControlFlash using that.
 

Similar Topics

Hi everyone, I am working with micro850, a proximity sensor (FOTEK, PL-05P) and a 3DOF serial arm robot. I use MC_MoveRelative to control the...
Replies
1
Views
49
HI everyone! I am trying to use a Micro850 to control a SureStep (Leadshine) Stepper drive (DM805-AI) from Automationdirect. I have no trouble...
Replies
7
Views
171
Hi guys, I have had some issues with uploading a program from a Micro 850 PLC. This is the first time connecting so I don’t have a file on my...
Replies
8
Views
271
I'm using a Micro850 with a Panelview 800, programming in CCW. We'd like the customer to be able to schedule the system to startup at a certain...
Replies
5
Views
123
Currently a student, so somewhat new to this. But working with an AB 2080-LC50-24QWB, CCW version 21.01.00. CCW will connect okay to the Micro850...
Replies
9
Views
290
Back
Top Bottom