B & R ACOPOS 1090 error

All the errors are described in the Automation Studio help. Error 9002 is heatsink temperature sensor not connected or damaged.

EDIT: Just download the trial version of automation studio, it will include their complete help file. Every error number has a little write-up about what causes it and possible fixes. Your PLC program probably also has a screen that displays the error text built into the PLC program automatically that would tell you what these error numbers mean.
 
Last edited:
Hi all,
Did you solve this problem?
I have a Acopos 1180, and it get error 7210, 7215. I tried to replace new 3 3nf capacitors but errors still happen.
Thank you.
 
Hi,
I'm sorry.I not good english.
Used B&R Automation Studio communication with Acopos 1090 find >>>>
error code:7210 DC Bus:Charging :Voltage unstable

You can change Capacitor value 0.033uF/275Vac.
Acopos 1090 connect 3 phase input.

Email:[email protected]





show.php
Hi, Could you please tell me how to read error code of Acopos in Automation Studio, Thanks you.
 

9030: Junction temperature model: Overtemperature - Movement stopped
LA solution s'il vous plait​

 

Similar Topics

Hello All...good day...really need help here...We got acopos 1090 behaving like really faulty. During power-up the ready and run led were...
Replies
1
Views
1,481
Our newish spray booth has the reciprocating arm driven by an acopos 1090 drive. HMI declares "reciprocating drive alarm" this happens several...
Replies
0
Views
1,210
is there is any error list code for both acopos drives , i got the same errors at both with out any description , the errors number is 15206 ...
Replies
1
Views
1,502
hay its me again the red LED on the drive is flashing it flashes five times then pause for a few second and it keeps on repeating that, can anyone...
Replies
1
Views
2,204
Hello, I'm trying to test Acopos multi using Automation Studio. Ready LED is green blinking, how can i know what error of Acopos on Automation...
Replies
1
Views
97
Back
Top Bottom