NAT Router - 1783-NATR Alternatives
Hello,
Does anyone have suggestions for an alternative to the AB 1783-NATR router? I need something in similar physical size but hoping to find one cheaper. Space is very limited in these panels so the smaller the better. Thanks in advance. |
![]() |
![]() |
#2 |
Lifetime Supporting Member + Moderator
|
They don't get much more compact than the Moxa NAT-102.
Is purchase price or footprint your primary criteria ? I haven't used the 102 but my general impression is that the Moxa NAT devices are a little trickier to set up, but are reasonably well documented. |
![]() |
![]() |
#3 |
Lifetime Supporting Member
|
RevPi is an industrial Linux computer can accomplish 1:1 NAT with a little linux-fu. Nice thing, once you have it working, you can script the configuration.
https://revolutionpi.com/forum/viewtopic.php?t=1301
__________________
Open source python communications library for CompactLogix/ControlLogix/Micro800 PLC's: https://github.com/dmroeder/pylogix |
![]() |
![]() |
#4 |
Lifetime Supporting Member
|
Slightly Off topic. Can someone explain purpose of a NAT router? And what issue it solves?
|
![]() |
![]() |
#5 |
Lifetime Supporting Member
|
Item (ii) below.
Servers need to be accessible to clients; clients need to be accessible to no one. There are (relatively) few servers but many clients. Many, many, clients. Many more clients needing addresses than are available in the 32-bit (4-octet) IP address space; also more clients in an organization than are available in that organization's purchased IP address allocation. NAT essentially hides many clients behind one IP address; futhermore, NATs can be stacked. That is, all clients behind a NAT router with its WAN port on The Internet appear to The Internet as if they all have the same IP address i.e. that of the WAN side of the NAT router. Each client typically makes few connections at any given time; servers typically have many connections made to them. The WAN side (one IP address) of a NAT router can make many proxy client connections, one for each of the actual client connections behind the NAT router; all it takes is a bit of bookkeeping. Cf. https://github.com/drbitboy/nat
__________________
_ Brian T. Carcich i) Take care of the bits, and the bytes will take care of themselves. ii) There is no software problem that cannot be solved with another layer of indirection. iii) Measurement is hard. iv) I solemnly swear that I am up to no good ![]() |
![]() |
![]() |
#6 |
Lifetime Supporting Member
|
Thanks for the explanation.
Cheers. |
![]() |
![]() |
#7 |
Lifetime Supporting Member + Moderator
|
Another reason.
As machine supplier, you supply 10 identical machines to one customer. Each machine have many networking devices (CPUs, HMIs, IO, Drives, ..). You want to not change the networking on each machine, but still be able to connect further up to a supervisory system. The NAT router solves this.
__________________
Jesper ![]() NOTICE: JesperMP can be impolite, has passive-aggressive tendencies and may use sarcasm ! |
![]() |
![]() |
#8 |
Lifetime Supporting Member
|
|
![]() |
![]() |
#9 | |
Lifetime Supporting Member
|
Quote:
__________________
Certified Siemens Functional Safety Professional, ID: SFSP17010238 NRA Benefactor |
|
![]() |
![]() |
#10 |
Member
|
Stratix Managed switches are also NAT capable depending on which ones you buy. I've used Stratix 5700 in the past with layer 2 NAT like the 1783-NATR, Stratix 5800 also comes with Layer 3 NAT, like the 9300ENA.
__________________
Ask not what your PLC can do for you, ask what you can do for your PLC. ![]() |
![]() |
![]() |
#11 |
Lifetime Supporting Member
|
LOL, that negates the OP's 2 requirements, save space and money over the NATR.
__________________
Open source python communications library for CompactLogix/ControlLogix/Micro800 PLC's: https://github.com/dmroeder/pylogix |
![]() |
![]() |
#12 | |
Member
|
Quote:
You can have multiple VLANs on the Stratix switches, so you can in theory use the same one switch for multiple NAT connections. Saving money and space. I think one stratix was about 5K, each NATR was about 1.5k. You can setup 7 VLANs on the 8 port Stratix 5700, and NAT+ route them to the plant network via the 8th port. Better cost proposition. Make room in a single panel, then drop ethernet to different local panels, space proposition also.
__________________
Ask not what your PLC can do for you, ask what you can do for your PLC. ![]() |
|
![]() |
![]() |
#13 | |
Lifetime Supporting Member
|
Quote:
__________________
Open source python communications library for CompactLogix/ControlLogix/Micro800 PLC's: https://github.com/dmroeder/pylogix |
|
![]() |
![]() |
#14 |
Member
![]() ![]() Join Date: May 2021
Location: United States
Posts: 4
|
The Hirschmann Eagle One can be configured for 1:1 NAT; it has a lot more complexity than the 1783-NATR but is more powerful too.
|
![]() |
![]() |
#15 | |
Member
![]() ![]() Join Date: Mar 2012
Location: Savannah, GA
Posts: 87
|
Quote:
|
|
![]() |
![]() |
Bookmarks |
Currently Active Users Viewing This Thread: 1 (0 members and 1 guests) | |
Thread Tools | |
Display Modes | |
|
|
![]() |
||||
Thread | Thread Starter | Forum | Replies | Last Post |
Communicating with PLC through NAT | wllewis84 | LIVE PLC Questions And Answers | 11 | April 13th, 2022 05:20 PM |
Using 1783 NATR with Siemens S7 PLCs. | PreLC | LIVE PLC Questions And Answers | 7 | October 1st, 2021 12:36 PM |
Alternatives to Rockwell NAT devices ? | passwordg | LIVE PLC Questions And Answers | 5 | January 28th, 2021 12:25 PM |
1783 natr | cyber14 | LIVE PLC Questions And Answers | 6 | January 31st, 2019 07:44 PM |
1783 natr cidr | Shlzy | LIVE PLC Questions And Answers | 3 | July 5th, 2018 05:56 PM |