We have boiler control system runs on A-B PLC. The interface is A-B Panel View Plus 7, mounted on the local control panel very near the boiler...
Replies
7
Views
93
I am installing a kinetix 5100 on a machine, driving a MPL servo, and it's my first time tuning a servo PID. I'm happy enough with the behavior of...
Replies
7
Views
86
So the customer purchased a Mitsubishi drive, in the same project for a different pump they got an ABB drive, was literally whatever they could...
Replies
1
Views
29
Hello, I have a question about an encoder that has absolute measurement. Specifically, it's the Lika SMA5, which I would like to connect...
Replies
9
Views
140
Hi all, I am trying to register EDS Files for IO Link in RSLogix V36.11 and anytime I use the "Device Description Installation Tool", it seems...
Replies
1
Views
17
Hi! When is CASE preffered? CASE uses a numreric variable for the cases and doesnt handle BOOL, but this can be done with numreric and bool using...
Replies
4
Views
96
Replies
3
Views
1,479
So i need to communicate my VFD (LS Electric iS7) with XGL PMEB module i successfully set the gsd file now i cant figure out how the data works...
Replies
0
Views
20
i am using profibus, i want to insert a hexadecimal word or byte to 4 byte like in the phot but i don't know how
Replies
5
Views
46
I´ve being trying wrap head around FOR loops.. When and what can this be used for? I´ve mostly seen it move data, resettting arrays etc. I made a...
Replies
4
Views