EICS
Member
Australia

EICS is offline
 
EICS's Avatar
 
Join Date: Dec 2008
Location: Melbourne, Australia
Posts: 269
Connected Components Workbench - HMI Issue

First Time CCW user, been using all rockwells other suites for years.

I have CCW V13 installed and have configured my PLC and HMI (the HMI tools are terrible if you have used FTV for years) and have them communicating and my project is 90% completed.

my issue is transferring the application to HMI, i cannot seem to get the comms to work from my machine and i am transferring the application to the terminal via USB stick as an export file from CCW as i have spent way too long trying to get the comms to work.

can anyone give me hints on how to config the HMI to accept direct downloads for my machine. its a 2711R-T7T Panelview 800

i have set the terminal to IP 192.168.0.101 my machine is on 192.168.0.230 but i cannot get it to see the terminal. i have tried Serial as well. i have no idea whats wrong.

what are the options for downloads direct to terminal ?


i see the terminal has

-DB9 port ( which is what the PLC is connected to)
-USB micro Port
-Ethernet port.
-USB A port(which i am using)
  Reply With Quote
Old July 29th, 2021, 06:09 AM   #2
EICS
Member
Australia

EICS is offline
 
EICS's Avatar
 
Join Date: Dec 2008
Location: Melbourne, Australia
Posts: 269
Anyone ?
  Reply With Quote
Old July 29th, 2021, 06:18 AM   #3
alan_505
Lifetime Supporting Member
Australia

alan_505 is offline
 
Join Date: Feb 2007
Location: Melbourne,Victoria,Australia
Posts: 697
I gave up trying to transfer the file by ethernet and used a USB stick that was very easy on the PV800.

Alan
  Reply With Quote
Old July 29th, 2021, 06:35 AM   #4
EICS
Member
Australia

EICS is offline
 
EICS's Avatar
 
Join Date: Dec 2008
Location: Melbourne, Australia
Posts: 269
Yes that's what I am doing too, thanks for the reply Alan

Regards
Alan
  Reply With Quote
Old July 29th, 2021, 08:46 PM   #5
bill4807
Member
United States

bill4807 is offline
 
Join Date: Mar 2013
Location: michigan
Posts: 226
I tried connecting with ethernet 1 time. Didnt work, but that was 3 panels ago.
Ever since i have just used the USB. Never tried ethernet again on those panels.
  Reply With Quote
Old July 30th, 2021, 01:24 AM   #6
DaveW
Member
United States

DaveW is offline
 
Join Date: Apr 2005
Location: SoCal
Posts: 377
I had a similar issue on a recent project. Found a tech note that says to connect the Ethernet cable from the PC directly to the Panelview and that worked for me. A little nuisance having to disconnect/reconnect to the PLC to during testing but project is done and I don't have to deal with this again for a while I hope.
  Reply With Quote
Old August 2nd, 2021, 10:18 AM   #7
Yashka
Member
United States

Yashka is offline
 
Join Date: Nov 2019
Location: WV
Posts: 78
What's the problem? It's very easy if you are in one local network with the panel.
1. Double-click to the HMI application in the left project tree window.
2. Choose the communication path in the right upper corner of this screen
3. Click the "Verify" button and then the "Download" button.
  Reply With Quote
Old August 3rd, 2021, 10:23 AM   #8
josalz
Member
United States

josalz is offline
 
Join Date: Jan 2020
Location: Rice Lake, Wisconsin
Posts: 10
Hmmm.... I'm a little confused as to why you had so much difficulty downloading via Ethernet. I did a project a couple of years ago for a customer and never had a problem. I actually deployed several updates via Ethernet remotely over a VPN and still didn't have any problems. Maybe it's a software version/compatibility issue with your machine? I'm kind of at a loss. Without an Ethernet option for application updates, the PV800 product would be just about useless for me, and I've been using them ever since they came out. Maybe I've just been lucky.
  Reply With Quote
Old August 3rd, 2021, 04:39 PM   #9
EICS
Member
Australia

EICS is offline
 
EICS's Avatar
 
Join Date: Dec 2008
Location: Melbourne, Australia
Posts: 269
well it seems its a firmware problem, see below from rockwell site.



Corrected Anomalies

This release corrects the following anomalies.

Terminal does not appear in RSLinx Classic software
Corrected Anomaly with Firmware Revision 6.012
Known Anomaly First Identified as of Firmware Revision 5.013
Catalog Numbers:
  • 2711R-T4T
  • 2711R-T7T
  • 2711R-T10T


In RSLinx® Classic software, the terminal does not appear under the RSWho window if the terminal is connected to the network.


i did upgrade the firmware to V6.011 in the terminal as soon as i got it, looks like they have only just released this later version a week or so ago.



I will download and upgrade and then report back.
  Reply With Quote
Reply
Jump to Live PLC Question and Answer Forum

Bookmarks


Currently Active Users Viewing This Thread: 1 (0 members and 1 guests)
 
Thread Tools
Display Modes

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off

Forum Jump

Similar Topics
Thread Thread Starter Forum Replies Last Post
Tag Editor Scaling in Connected Components Workbench jrsnydley LIVE PLC Questions And Answers 9 October 30th, 2018 06:59 AM
Connected Components Workbench Question ref JSR instruction Robomah LIVE PLC Questions And Answers 6 March 2nd, 2018 06:10 PM
Upgrade Connected Components Workbench KevinIowa LIVE PLC Questions And Answers 3 May 16th, 2017 02:07 PM
Connected components workbench: HMI Trends blackbird307 LIVE PLC Questions And Answers 3 August 12th, 2016 11:34 AM
Tag address issues with connected components workbench. Grumbley3 LIVE PLC Questions And Answers 0 August 12th, 2016 12:51 AM


All times are GMT -4. The time now is 05:06 PM.


.