hi i have a poroblem with this jumo pressure metter
-1 to 0.6bar 4-20ma and i connencted with 2 wire connection to plc, On this pictures whit this post you can se it is showing 0.67 bar but it is no pressure on it ?

pressure.jpg
 
Remove the pressure sensor and make sure it reads zero or there abouts in the air.

My suspicion is the shut off valve is close to the pressure transducer and you have compressed the air sample,
or
You have liquid sample that is hydraulic ing as the sample warms up and expands in the pipe line.

Try opening the sample shut off valve and see if your readings come correct as 1.6 bar or 25 psi is a narrow span and you are only 0.6 bar or 9 psi above atmosphere
 
Remove the pressure sensor and make sure it reads zero or there abouts in the air.

My suspicion is the shut off valve is close to the pressure transducer and you have compressed the air sample,
or
You have liquid sample that is hydraulic ing as the sample warms up and expands in the pipe line.

Try opening the sample shut off valve and see if your readings come correct as 1.6 bar or 25 psi is a narrow span and you are only 0.6 bar or 9 psi above atmosphere

i have the pressure sensore on my desk and he is brand new
 
Have you measured the actual milliamp signal into your PLC?

If the transmitter is open to atmosphere then the output of the transmitter is about right. ( maxed out)

1 Bar = .98 atmosphere
 
Last edited:
What is the number of the input card, as those values for input min and input max don't ring a bell with me and the 21816 is close to a zero value if 15 bits are used

0 to 21 equaling 0 to 32767
 
Last edited:
What is the number of the input card, as those values for input min and input max don't ring a bell with me and the 21816 is close to a zero value if 15 bits are used

0 to 20 equaling 0 to 32767


Some AB cards have an "Engineering Unit" data format which give you 4000 counts at 4ma and 20000 counts at 20ma. That is probably how the OP has it configured.
 
Some AB cards have an "Engineering Unit" data format which give you 4000 counts at 4ma and 20000 counts at 20ma. That is probably how the OP has it configured.

Yes Mickey, I know what you mean there are quite a few possibilities until we get the card number and then his configuration of that card,
or maybe a wiring error.
 
hi i have a poroblem with this jumo pressure metter
-1 to 0.6bar 4-20ma and i connencted with 2 wire connection to plc, On this pictures whit this post you can se it is showing 0.67 bar but it is no pressure on it ?

the problem was "inpud min 6240 / inpud max 31200" works great now
 
you have to calibrate it and get the actual values from sensor. btw your first reading was above max so the calcs were correct.
if you make these values in VARs you can change the calibration in the field while the plc is running.
 

Similar Topics

The project on the operator workstation keeps disconnecting, even though I have an installation server and operating station set up through...
Replies
0
Views
21
I have a problem, I'm running an AE Licence Manager on a Windows 2016 Server, and my Window Maker is on another separate Windows 2016 Server. My...
Replies
0
Views
37
I have one old Ansaldo VFD from 37kW and it have only sign OFF on the display after put it on the 3x400VAC. Is there any idea, how to solve this...
Replies
0
Views
31
Hello, I need to write the following program in Ladder language, but I could not integrate the Fibonacci sequence into the ladder. Can you help...
Replies
22
Views
483
On all pages of my project i have a lot of information, texts and details that should not not be shown. I can remove them for each part apart from...
Replies
0
Views
64
Back
Top Bottom