hi everyone, I'm new with plc, and am trying to connect cpu 313c with pc via MPI usb cable. Plc is set to run a FESTO pick and place station.
I have established a MPI connection between PG/PC and SIMATIC 300 station. But when configuring hardware there are no modules that I need in the hardware library even after I have updated the library.o_O Actually I'm not sure if the network connection is correct so I really need help! So if anyone knows how exactly to configure the hardware and make pick and place station run I would be very gratefull :D
 
I have established a MPI connection between PG/PC and SIMATIC 300 station. But when configuring hardware there are no modules that I need in the hardware library even after I have updated the library.

Is this on a machine that is running or is it a new CPU? if its an older running machine you should be able to upload the configuration from the CPU using the MPI that you have connected, are you using Step7 5.5 ?
 
What do you mean by older running machine? CPU is 313c. Pick and place station can be started manually without the plc so there is no problem there, all the sensors are on and working...I am using SIMATIC S7 v.5.5. How can the configuration be uploaded exactly? I have tried by clicking upload but all it does is show cpu 313c in the configuration rack and no i/o modules...

the station is exactly like this one:

http://www.youtube.com/watch?v=-_u26B0ecZ8
 
Last edited:
What modules do you have physically?

Is it FESTO or are you talking about Siemens Modules? If it is FESTO it will likely be profibus/profinet, you will have to install the appropriate GSD files.

If it is Siemens, what are the module order numbers?
 
It is Siemens the order number for the CPU 313C is 6ES7 313-5BF03-0AB0 v.2.6.9
Where can I find the order numbers for the modules? It says DI8XDC24V AI5/AO2X12Bit and on the other one DI16/DO16XDC24V just like in this picture
siemens-cpu313c-6es7-313-5be01-0ab0-simatic-s7-3427.html
 
Those are the integrated in and outputs for the 313C and are automatically added to the hardware when you add the CPU to your HW. Just double click AI5/AO2 shown in the left of the picture and you can change from Volt input/output to Current.

On the bottom you see your addresses.

Capture.png
 
oh I see so thats it for HW config rack? I dont have to add anything else?
What kind of connection is best? Is it ok to use MPI? I have been configuring hardware using something an exchange student wrote, (the file is too big to post here) so I'm not sure if its correct but its the only thing I have to go by..
 
the 313C you mention only will do MPI, so you should be ok. you can send me a PM for my email addy if you would like me to look over your code.

good luck!
 
Back up for Step 7 is a ZIP containing a folder.
Back up for TIA is a .zap12 (and .zap11 I imagine) containing a folder

I don't know what would use an .EXE..

Edit:
The .exe you mention is a self extracting archive. Run it. In the folder that is extracted you will find 4 zipped folder which you can RETRIEVE with Simatic Manager.
 
Last edited:

Similar Topics

HI everyone, i am new to Siemens plc programming and i am in need of some help. yesterday we had an S7-1200 CPU 1214C fail to turn on an output to...
Replies
7
Views
203
Hello, good morning, I have been having two problems with the Tia Portal software. The first is that I have installed it on my computer and...
Replies
5
Views
192
The past week we received a new piece of equipment from Germany which utilizes siemens controls. Typically in our company we use A.B. controls for...
Replies
12
Views
353
i have two plc 1. s7-1212dc/dc/dc ip; 192.168.0.1 2. s7-1500 1513-1pn ip; 192.168.3.2 i need to get data from plc1 to plc2. any idea how to do...
Replies
5
Views
166
Good morning fellow sea captains and wizards, I am being asked to do the above and obtain 4 values from each slave, I know about the MRX and MWX...
Replies
32
Views
952
Back
Top Bottom