Hi, and thanks for your reply.
I'm not going through a switch at the moment, so that's not it. I feel good about the cables as you've mentioned.
I get the USB driver that you mentioned however the module shows as an unrecognized device. I believe as I replied to someone below, that I will have to get EDS files from Rockwell, along with upgrading Linx as you pointed out. I have V. 32.01 now and this is what I ended up loading in this project, as the L73S only offered that version of firmware. So maybe Linx is already up to date, I'll see.
Since this is a stand-alone system, no plant connection, no FIS, no nothing, I could easily use the rotary switches. I may just use all this knowledge from you guys to configure a new EN2T in the main plant. We're undergoing a re-tool, and I'll have plenty of opportunities. Thank you.
Setting an IP Address on the EN2T by any means mentioned will not resolve the issue that RSLinx doesn't recognise it.
For that to be resolved you have to install the EDS file using the proper installation wizard.
The EN2T will be new enough for you to be able to get the EDS file from the device itself. Simply right-click it in RSLinx, and choose "Upload EDS File from Device". This will get the EDS file AND launch the EDS file installation wizard. Just follow the prompts and it all happens very smoothly.
Once the EDS is installed, RSLinx should recognise it.